NonLockout Ignition Control Uni-Kit
  • Robertshaw's Universal Ignition Control Uni-Kits feature a flame sense circuit that will work equally well on a one rod (local sense) or a two rod (remote sense) application.
  • The automatic recycle features assure that, in the event of flame failure, main gas is disabled and the spark repetition sequence is restarted until pilot gas is ignited. Only after pilot ignition has been re-established can main gas be returned to the burner.
  • Replaces one rod and/or two rod systems.
  • Reduces truck stock inventory, saving space and money.
  • Includes vent damper adaptor assembly.
  • Easy-to-install with complete in-depth installation instructions.
  • Replaces Robertshaw, Johnson Controls, and Honeywell


Specifications:
  • Input Voltage24 VAC to 50/60 Hz
  • Transformer24 VAC / 20 VA
  • Spark rate3 to 4 sparks per second
  • Pilot valve, Main valve1 amp at .5 PFCombined load1.5 at .4
  • PFFlame sense current.7 mA DC @ 25°C / 24 VAC
  • Maximum total current load1.5 amp
  • Flame failure reignition time.8 seconds
  • maximumThermostat anticipator setting.7 amp
  • Ambient temperature rating-40 to 175° (-40 to 80°C)


Specifications

NameNonLockout Ignition Control Uni-Kit
Gemaire Item Number780-001
Manufacturer Product Number780-001
SKU - PIM Number1372691425165
ERP Number292953
Unit of MeasureEA
Weight0.6 Pounds (Lb)
Length1.5 Inches (In)
Width5.0 Inches (In)
Height3.3 Inches (In)
Country of OriginMEX
BrandRobertshaw